List of Faults and Alarms
Faults and Alarms
3-633
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
A08752
CAN: Error counter for error passive exceeded
Reaction:
NONE
Acknowledge:
NONE
Cause:
The error counter for the send or receive telegrams has exceeded the value 127.
Remedy:
- check the bus cable
- set a higher baud rate (p8622).
- check the bit timing and if required optimize (p8623).
See also: p8622 (CAN baud rate), p8623 (CAN Bit Timing selection)
A08753
CAN: Message buffer overflow
Reaction:
NONE
Acknowledge:
NONE
Cause:
A message buffer overflow.
Alarm value (r2124, interpret decimal):
1: Non-cyclic send buffer (SDO response buffer) overflow.
2: Non-cyclic receive buffer (SDO receive buffer) overflow.
3: Cyclic send buffer (PDO send buffer) overflow.
Remedy:
Check the bus cable.
Set a higher baud rate (p8622).
Check the bit timing and if required optimize (p8623).
Alarm value = 2:
- reduce the cycle times of the SDO receive messages.
- SDO request from master only after SDO feedback for previous SDO request.
See also: p8622 (CAN baud rate), p8623 (CAN Bit Timing selection)
A08754
CAN: Incorrect communications mode
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the "operational" mode, an attempt was made to change parameters p8700 ... p8737.
Remedy:
Change to the "pre-operational" or "stopped" mode.
A08755
CAN: Object cannot be mapped
Reaction:
NONE
Acknowledge:
NONE
Cause:
The CANopen object is not provided for the Process Data Object (PDO) Mapping.
Remedy:
Use a CANopen object intended for the PDO mapping or enter 0.
The following objects can be mapped in the Receive Process Data Object (RPDO) or Transmit Process Data Object
(TPDO):
- RPDO: 6040 hex, 6060 hex, 60FF hex, 6071 hex; 5800 hex - 580F hex; 5820 hex - 5827 hex
- TPDO: 6041 hex, 6061 hex, 6063 hex, 6069 hex, 606B hex, 606C hex, 6074 hex; 5810 hex - 581F hex; 5830 hex
- 5837 hex
Only sub-index 0 of the specified objects can be mapped.
Note:
As long as A08755 is present, the COB-ID cannot be set to valid.
A08756
CAN: Number of mapped bytes exceeded
Reaction:
NONE
Acknowledge:
NONE
Cause:
The number of bytes of the mapped objects exceeds the telegram size for net data. A max. of 8 bytes is permissible.
Remedy:
Map fewer objects or objects with a smaller data type.
See also: p8710, p8711, p8712, p8713, p8714, p8715, p8716, p8717, p8730, p8731, p8732, p8733, p8734, p8735,
p8736, p8737
Содержание CU230P-2 CAN
Страница 1: ...s SINAMICS G120 Control Units CU230P 2 Parameter Manual 11 2009 SINAMICS ...
Страница 2: ......
Страница 666: ...Index C 666 Siemens AG 2009 All Rights Reserved SINAMICS G120 Control Units CU230P 2 Parameter Manual LH9 11 2009 ...
Страница 667: ......