Parameters
List of Parameters
1-276
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the signal source for the setpoint 2 of the technology controller.
Dependency:
Refer to: p2253, p2256
Description:
Sets the scaling for the setpoint 1 of the technology controller.
Dependency:
Refer to: p2253
Description:
Sets the scaling for the setpoint 2 of the technology controller.
Dependency:
Refer to: p2254
Description:
Sets the ramp-up time of the technology controller.
Dependency:
Refer to: p2258
Note:
The ramp-up time is referred to 100 %.
Description:
Sets the ramp-down time of the technology controller.
Dependency:
Refer to: p2257
Note:
The ramp-down time is referred to 100 %.
Description:
Sets the setpoint after the ramp-function generator of the technology controller.
p2254[0...n]
CI: Technology controller setpoint 2 / Tec_ctrl setp 2
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
CDS, p0170
Min Max Factory
setting
- - 0
p2255
Technology controller setpoint 1 scaling / Tec_ctrl set1 scal
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [%]
100.00 [%]
100.00 [%]
p2256
Technology controller setpoint 2 scaling / Tec_ctrl set2 scal
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [%]
100.00 [%]
100.00 [%]
p2257
Technology controller, ramp-up time / Tec_ctrl t_ramp-up
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [s]
650.00 [s]
1.00 [s]
p2258
Technology controller ramp-down time / Tec_ctrl t_ramp-dn
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [s]
650.00 [s]
1.00 [s]
r2260
CO: Technology controller setpoint after ramp-function generator /
Tec_ctr set aftRFG
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT