List of Parameters
Parameters
1-313
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the Pre-defined Error Field of the CAN node.
It includes the number of all errors that have occurred, the number of errors that have occurred for each drive and
the errors according to their history.
The first 16 bits represent the CANopen error code and the second 16 bits the SINAMICS error code.
Index 1 has the same structure - however, the drive object ID is in the second 16 bits instead of the SINAMICS error
code.
CANopen error code:
0000 hex: No error present
8110 hex: Alarm A08751 present
8120 hex: Alarm A08752 present
8130 hex: Alarm A08700(F) with alarm value = 2 present
1000 hex: Generic error 1 present (there is at least one fault outside the range 8700 ... 8799)
1001 hex: Generic error 2 present (there is at least one alarm in the range 8700 ... 8799 with the exception of
A08751, A08752, A08700)
All drive objects are acknowledged by writing the value 0 to the index 0. As soon as a fault has been acknowledged
or an alarm cleared, then it is also cleared from the fault list.
Index:
[0] = Number of all faults in the drive unit
[1] = Most recent drive number / fault number
[2] = Number of faults drive 1
[3] = Fault 1/ drive 1
[4] = Fault 2/ drive 1
[5] = Fault 3/ drive 1
[6] = Fault 4/ drive 1
[7] = Fault 5/ drive 1
[8] = Fault 6/ drive 1
Note:
Corresponds to the CANopen object 1003 hex.
Description:
Display or setting of the CANopen Node ID.
The Node ID can be set as follows:
1) Using the address switch on the Control Unit.
--> p8620 can then only be read and displays the selected Node ID.
--> A change only becomes effective after a POWER ON.
--> CANopen Node ID and PROFIBUS address are identical.
2) Using p8620
--> only if all of the DIP switches - from S1 to S7 - are either set to ON or OFF.
--> the Node ID is set as standard to 126.
--> A change only becomes effective after save and POWER ON.
Notice:
For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
Every node ID change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
It is only possible to independently set CANopen node ID and the PROFIBUS address using p0918 and p8620 (pre-
requisite: For DIP switches, all of the switches from S1 to S7 are either set to ON or OFF).
p8611[0...82]
CAN Pre-defined Error Field / Pre_def err field
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0000 hex
FFFF 1000 hex
0000 hex
p8620
CAN Node-ID / Node ID
CU230P-2 CAN
Access level:
2
Calculated:
-
Data type:
Unsigned8
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
1 126
126