List of Parameters
Parameters
1-395
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Setting parameter for the run-time group in which the instance NCM 1 of the numeric comparator is to be called.
Value:
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
Description:
Setting parameter for the run sequence of instance NCM 1 within the run-time group set in p20322.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description:
Sets the signal source for set input S and reset input R of instance RSR 2 of the RS flipflop.
Index:
[0] = Set S
[1] = Reset R
Description:
Display parameter for output Q of instance RSR 2 of the RS flipflop
Description:
Display parameter for inverted output QN of instance RSR 2 of the RS flipflop.
Description:
Setting parameter for the run-time group in which instance RSR 2 of the RS flipflop is to be called.
Value:
1:
Run-time group 1
2:
Run-time group 2
3:
Run-time group 3
4:
Run-time group 4
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
p20322
NCM 1 run-time group / NCM 1 RTG
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
5 9999
9999
p20323
NCM 1 run sequence / NCM 1 RunSeq
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 32000
830
p20324[0...1]
BI: RSR 2 inputs / RSR 2 inputs
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
- - 0
r20325
BO: RSR 2 output Q / RSR 2 output Q
Access level:
3
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-
r20326
BO: RSR 2 inverted output QN / RSR 2 inv outp QN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-
p20327
RSR 2 run-time group / RSR 2 RTG
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
1 9999