List of Parameters
Parameters
1-55
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Resistance of the power cable between the power unit and motor.
Caution:
The cable resistance should be entered prior to motor data identification. If it is used subsequently, the difference
by which p0352 was changed must be subtracted from the stator resistance p0350 or motor data identification must
be repeated.
Note:
The parameter influences the temperature adaptation of the stator resistance.
The motor identification sets the cable resistance to 20% of the measured total resistance if p0352 is zero at the
time that the measurement is made. If p0352 is not zero, then the value is subtracted from the measured total stator
resistance to calculate stator resistance p0350. In this case, p0350 is a minimum of 10% of the measured value.
The cable resistance is reset when quick commissioning is exited with p3900 > 0.
Description:
Sets the rotor/secondary section resistance of the motor at the ambient temperature p0625.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910).
Dependency:
Refer to: p0625
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter is not used for synchronous motors (p0300 = 2).
Description:
Induction machine: sets the stator leakage inductance of the motor.
Synchronous motor: Sets the stator quadrature axis inductance of the motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910).
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
If the stator leakage inductance (p0356) for induction motors is changed outside the commissioning phase (p0010 >
0), the magnetizing inductance (p0360) is automatically adapted to the new EMF (r0337). You are then advised to
repeat the measurement for the saturation characteristic (p1960).
For permanent-magnet synchronous motors (p0300 = 2), this is the non-saturated value and is, therefore, ideal for
a low current.
p0352[0...n]
Cable resistance / Mot R_cable cold
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Data set:
MDS
Min Max Factory
setting
0.00000 [Ohm]
120.00000 [Ohm]
0.00000 [Ohm]
p0354[0...n]
Motor rotor resistance cold / Mot R_r cold
Access level:
3
Calculated:
p0340 = 1,2
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Data set:
MDS
Min Max Factory
setting
0.00000 [Ohm]
300.00000 [Ohm]
0.00000 [Ohm]
p0356[0...n]
Motor stator leakage inductance / Mot L_stator leak.
Access level:
3
Calculated:
p0340 = 1,2
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Data set:
MDS
Min Max Factory
setting
0.00000 [mH]
1000.00000 [mH]
0.00000 [mH]