Parameters
List of Parameters
1-156
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the status of the automatic restart (AR).
Note:
Re bit 00:
State to display the single initialization after POWER ON.
Re bit 01:
State in which the automatic restart function waits for faults (initial state).
Re bit 02:
General display that a fault has been identified and that the restart or acknowledgement has been initiated.
Re bit 03:
Displays the acknowledge command within the "acknowledge alarms" state (bit 4 = 1). For bit 5 = 1 or bit 6 = 1, the
acknowledge command is continually displayed.
Re bit 04:
State in which the faults that are present are acknowledged. The state is exited again after successful acknowl-
edgement. A change is only made into the next state if it is signaled that a fault is no longer present after an
acknowledgement command (bit 3 = 1).
Re bit 05:
State in which the drive is automatically powered up (only for p1210 = 4, 6).
Re bit 06:
State in which the system waits after having been powered up, to the end of the start attempt (to the end of the
magnetizing process).
For p1210 = 1, this signal is directly set after the faults have been successfully acknowledged.
Re bit 07:
State which is assumed after a fault occurs within the automatic restart function. This is only reset after acknowl-
edging the fault and withdrawing the power-on command.
Re bit 10:
When the automatic restart function is active, r1214 bit 7 is displayed, otherwise the effective fault r2139 bit 3.
Re bits 12 ... 15:
Actual state of the start counter (binary coded).
r1214.0...15
CO/BO: Automatic restart, status / AR status
Access level:
4
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Initialization
Yes
No
-
01
Wait for alarm
Yes
No
-
02
Auto restart act
Yes
No
-
03
Setting the acknowledgement command
Yes
No
-
04
Acknowledge alarms
Yes
No
-
05
Restart
Yes
No
-
06
Delay time running after automatic power-
up
Yes
No
-
07
Fault
Yes
No
-
10
Effective fault
Yes
No
-
12
Start count. bit 0
On
Off
-
13
Start count. bit 1
On
Off
-
14
Start count. bit 2
On
Off
-
15
Start count. bit 3
On
Off
-