List of Parameters
Parameters
1-209
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the integral time for the Rs adaptation of the motor model for an induction motor (ASM).
Description:
Displays the corrective value for the Rs adaptation of the motor model for an induction motor (ASM).
Dependency:
Refer to: p0826, p1780
Note:
The display of the inactive data sets is only updated when changing over the data set.
Description:
Sets the proportional gain for the Rs adaptation of the motor model for an induction motor (ASM).
Description:
Sets the proportional gain for the Lh adaptation of the motor model for an induction motor (ASM).
Description:
Sets the integral time for the Lh adaptation of the motor model for an induction motor (ASM).
Description:
Displays the corrective value for the Lh adaptation of the motor model for an induction motor (ASM).
Dependency:
Refer to: p0826, p1780
Note:
The adaptation result is reset if the magnetizing inductance of the induction motor is changed (p0360, r0382). This
also happens when changing over the data set if a different motor is not being used (p0826).
The display of the inactive data sets is only updated when changing over the data set.
Description:
Displays the power-on stator frequency for the Rs adaptation for the induction motor (ASM).
p1781[0...n]
Motor model Rs adaptation integral time / MotMod Rs Tn
Access level:
4
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
10 [ms]
10000 [ms]
100 [ms]
r1782[0...n]
Motor model Rs adaptation corrective value / MotMod Rs corr
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Ohm]
Scaling:
-
Data set:
DDS, p0180
p1783[0...n]
Motor model Rs adaptation Kp / MotMod Rs Kp
Access level:
4
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.000 1.000 0.100
p1785[0...n]
Motor model Lh adaptation Kp / MotMod Lh Kp
Access level:
4
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.000 1.000 0.100
p1786[0...n]
Motor model Lh adaptation integral time / MotMod Lh Tn
Access level:
4
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
10 [ms]
10000 [ms]
100 [ms]
r1787[0...n]
Motor model Lh adaptation corrective value / MotMod Lh corr
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[mH]
Scaling:
-
Data set:
DDS, p0180
r1789
Motor model Rs adaptation switch-in frequency / MotMod Rs f_on
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Hz]
Scaling:
-
Data set:
-