Parameters
List of Parameters
1-214
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the configuration for the modulator.
Notice:
Bit 1 = 1 can only be set under a pulse inhibit and for r0192.14 = 1.
Note:
Bit 00 = 0:
Voltage limitation from the minimum of the DC link voltage (lower ripple in the output current, reduced output volt-
age).
Bit 00 = 1:
Voltage limitation from averaged DC link voltage (higher output voltage with increased ripple in the output current).
The selection is only valid if the DC link compensation is not performed in the Control Unit (bit 1 = 0).
Bit 01 = 0:
DC link voltage compensation in the modulator.
Bit 01 = 1:
DC link voltage compensation in the current control.
Description:
Sets the phase sequence reversal for the motor without setpoint change.
If the motor does not rotate in the required direction, then the output phase sequence can be reversed using this
parameter. This means that the direction of the motor is reversed without the setpoint being changed.
Value:
0:
Off
1:
On
Note:
This setting can only be changed when the pulses are inhibited.
Description:
Sets the threshold voltage drop of the valves (power semiconductor devices) to be compensated.
Note:
The value is automatically calculated in the motor data identification routine.
Description:
Sets the valve lockout time to compensate for phase U.
Note:
The value is automatically calculated in the motor data identification routine.
p1810
Modulator configuration / Modulator config
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
- - 0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Avg value filter for V_lim (only for
Vdc_comp. in modulator)
Yes
No
-
01
DC link voltage compensation in the current
control
Yes
No
-
p1820[0...n]
Reverse the output phase sequence / Outp_ph_seq rev
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
C(2), T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0 1 0
p1825
Converter valve threshold voltage / Threshold voltage
Access level:
4
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.0 [Vrms]
100.0 [Vrms]
0.6 [Vrms]
p1828
Compensation valve lockout time phase U / Comp t_lock ph U
Access level:
4
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [µs]
3.99 [µs]
0.00 [µs]