List of Parameters
Parameters
1-311
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the node guarding parameter for the following CANopen objects:
- 100C hex: Guard Time
- 100D hex: Life Time Factor
The life time is derived by multiplying guard time by the life time factor.
Index:
[0] = Time interval [ms] for new node guarding telegram
[1] = Factor for failure of the node guarding telegram
Dependency:
Only adjustable if heartbeat time = 0 (heartbeat is disabled).
Refer to: p8606
Note:
For p8604[0] = 0 and/or p8604[1] = 0, the node guarding protocol is not used.
Either node guarding or heartbeat can be used.
Description:
Sets the time [ms] to cyclically send heartbeat telegrams.
The smallest cycle time is 100 ms.
When a 0 is written, then heartbeat telegrams are not sent.
Dependency:
Only adjustable if guard time = 0 (node guarding disabled).
Refer to: p8604
Note:
Corresponds to the CANopen object 1017 hex.
Either node guarding or heartbeat can be used.
Description:
General device information display.
Index:
[0] = Vendor ID
[1] = Product code
[2] = Revision number
[3] = Serial number
Note:
Corresponds to the CANopen object 1018 hex.
Re index 3:
The SINAMICS serial number comprises 60 bits. Of these bits, the following are displayed in this index:
Bits 0 ... 19: Consecutive number
Bits 20 ... 23: Production ID
- 0 hex: Development
- 1 hex: P1 unique number
- 2 hex: P2 unique number
- 3 hex: WA unique number
- 9 hex: Pattern
- F hex: All others
Bits 24 ... 27: Month of manufacture (0 means January, B means December)
Bits 28 ... 31: Year of manufacture (0 means 2002)
p8604[0...1]
CAN node guarding / Node guarding
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 65535
0
p8606
CAN Producer Heartbeat Time / Prod Heartb Time
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 [ms]
65535 [ms]
0 [ms]
r8607[0...3]
CAN Identity Object / Identity object
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-