Parameters
List of Parameters
1-70
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the service/maintenance intervals in hours for the appropriate motor.
An appropriate fault is output when the operating hours set here are reached.
Dependency:
Refer to: p0650
Refer to: A01590
Note:
For p0651 = 0, the operating hours counter is disabled.
The operating hours counter only runs for DDS0 and DDS1 (Drive Data Set).
Description:
Sets the command source.
Value:
2:
Terminals
Note:
With PROFIBUS / PROFINET Control Units, p0922 = 999 must be set so that the command and setpoint sources
can be changed.
Description:
Sets the command source.
Value:
2:
Terminals
6:
Fieldbus
Note:
With PROFIBUS / PROFINET Control Units, p0922 = 999 must be set so that the command and setpoint sources
can be changed.
Description:
Sets the command source.
Value:
2:
Terminals
6:
Fieldbus
Note:
With PROFIBUS / PROFINET Control Units, p0922 = 999 must be set so that the command and setpoint sources
can be changed.
p0651[0...n]
Motor operating hours maintenance interval / Mot t_op maint
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
T
Scaling:
-
Data set:
MDS
Min Max Factory
setting
0 [h]
150000 [h]
0 [h]
p0700[0...n]
Command source selection / Cmd src sel
CU230P-2 CAN
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
2 2 2
p0700[0...n]
Command source selection / Cmd src sel
CU230P-2 DP
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
2 6 6
p0700[0...n]
Command source selection / Cmd src sel
CU230P-2 HVAC
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
2 6 2