List of Parameters
Parameters
1-21
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the actual temperature in the motor.
Note:
For r0035 not equal to -200.0 °C, the following applies:
- this temperature display is valid.
- a KTY sensor is connected.
- for induction motors, the thermal motor model is activated (p0601 = 0).
For r0035 equal to -200.0 °C, the following applies:
- this temperature display is not valid (temperature sensor error).
- A PTC sensor or bimetallic NC contact is connected.
- for synchronous motors, the thermal motor model is activated (p0601 = 0).
Description:
Displays the power unit overload determined using the I2t calculation.
A current reference value is defined for the I2t monitoring of the power unit. It represents the current that can be
conducted by the power unit without any influence of the switching losses (e.g. the continuously permissible current
of the capacitors, inductances, busbars, etc.).
If the I2t reference current of the power unit is not exceeded, then an overload (0 %) is not displayed.
In the other case, the degree of thermal overload is calculated, whereby 100% results in a trip.
Dependency:
Refer to: p0290, p0294
Refer to: F30005
Description:
Displays the temperatures in the power unit.
Index:
[0] = Inverter
[1] = Depletion layer
[2] = Reserved
[3] = Reserved
[4] = Interior of power unit
[5] = Inverter 1
[6] = Reserved
[7] = Reserved
[8] = Reserved
[9] = Reserved
[10] = Reserved
[11] = Reserved
[12] = Reserved
[13] = Depletion layer 1
[14] = Reserved
[15] = Reserved
[16] = Reserved
[17] = Reserved
[18] = Reserved
[19] = Reserved
Note:
The value of -200 indicates that there is no measuring signal.
r0035
CO: Motor temperature / Mot_temp
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[°C]
Scaling:
TEMP
Data set:
-
r0036
CO: Power unit overload I2t / PU overload I2t
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-
r0037[0...19]
CO: Power unit temperatures / PU temperatures
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[°C]
Scaling:
TEMP
Data set:
-