List of Parameters
Parameters
1-33
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the field-generating current actual value (Id_act).
Dependency:
Refer to: r0029
Note:
This value is irrelevant for the V/f control mode.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
Description:
Displays the torque/force generating current setpoint.
Note:
This value is irrelevant for the V/f control mode.
Description:
Displays the torque-generating current actual value (Iq_act).
Dependency:
Refer to: r0030
Note:
This value is irrelevant for the V/f control mode.
The torque-generating current actual value is available smoothed (r0030 with 300 ms) and unsmoothed (r0078).
Description:
Displays the torque setpoint at the output of the speed controller (before clock cycle interpolation).
Description:
Displays the actual torque value.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
Dependency:
Refer to: r0031
Note:
The torque actual value is available smoothed (r0031 with 100 ms, r0080[1] with p0045) and unsmoothed
(r0080[0]).
Description:
Displays the torque utilization as a percentage.
The torque utilization is obtained from the required smoothed torque referred to the torque limit.
Dependency:
This parameter is only available for vector control. For V/f control r0081 = 0 %.
Refer to: r0033
Note:
The torque utilization is available smoothed (r0033) and unsmoothed (r0081).
The torque utilization is obtained from the required torque referred to the torque limit as follows:
- Positive torque: r0081 = (r0079 / r1538) * 100 %
- Negative torque: r0081 = (-r0079 / -r1539) * 100 %
r0076
CO: Current actual value field-generating / Id_act
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Arms]
Scaling:
p2002
Data set:
-
r0077
CO: Current setpoint torque-generating / Iq_set
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Arms]
Scaling:
p2002
Data set:
-
r0078
CO: Current actual value torque-generating / Iq_act
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Arms]
Scaling:
p2002
Data set:
-
r0079
CO: Torque setpoint total / M_set total
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Nm]
Scaling:
p2003
Data set:
-
r0080[0...1]
CO: Torque actual value / M_act
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Nm]
Scaling:
p2003
Data set:
-
r0081
CO: Torque utilization / M_Utilization
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-