List of Faults and Alarms
Faults and Alarms
3-617
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
A07402 (N)
Drive: DC link voltage minimum controller active
Reaction:
NONE
Acknowledge:
NONE
Cause:
The DC link voltage controller has been activated as the lower switch-in threshold has been undershot (r1246,
r1286).
The kinetic energy of the motor is used to buffer the DC link. The drive is therefore braked.
See also: r0056 (Status word, closed-loop control), p1240 (Vdc controller or Vdc monitoring configuration (vector
control)), p1280 (Vdc controller or Vdc monitoring configuration (V/f))
Remedy:
The alarm disappears when power supply returns.
F07405 (N, A)
Drive: Kinetic buffering minimum speed not reached
Reaction:
OFF2 (IASC/DCBRAKE, NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
During kinetic buffering the speed fell below minimum speed (p1257 or p1297 for vector drives with V/f control) and
the line supply did not return.
Remedy:
Check the speed threshold for the Vdc_min controller (kinetic buffering) (p1257, p1297).
See also: p1257 (Vdc_min controller speed threshold)
F07406 (N, A)
Drive: Kinetic buffering maximum time exceeded
Reaction:
OFF3 (IASC/DCBRAKE, NONE, OFF1, OFF2, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
The maximum buffer time (p1255 and p1295 for vector drives with V/f control) has been exceeded without the line
supply having returned.
Remedy:
Check the time threshold for Vdc-min controller (kinetic buffering) (p1255, p1295).
See also: p1255 (Vdc_min controller time threshold)
A07409
Drive: V/f control, current limiting controller active
Reaction:
NONE
Acknowledge:
NONE
Cause:
The current limiting controller of the V/f control was activated because the current limit was exceeded.
Remedy:
The alarm is automatically withdrawn when increasing the current limit (p0640), reducing the load or using a slower
up ramp for the setpoint (reference) speed.
F07410
Drive: Current controller output limited
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
The condition "I_act = 0 and Uq_set_1 longer than 16 ms at its limit" is present and can be caused by the following:
- motor not connected or motor contactor open.
- motor data and motor configuration (star-delta) do not match.
- no DC link voltage present.
- power unit defective.
- the "flying restart" function is not activated.
Remedy:
- connect the motor or check the motor contactor.
- check the motor parameterization and the connection configuration (star-delta).
- check the DC link voltage (r0070).
- check the power unit.
- activate the "flying restart" function (p1200).
Содержание CU230P-2 CAN
Страница 1: ...s SINAMICS G120 Control Units CU230P 2 Parameter Manual 11 2009 SINAMICS ...
Страница 2: ......
Страница 666: ...Index C 666 Siemens AG 2009 All Rights Reserved SINAMICS G120 Control Units CU230P 2 Parameter Manual LH9 11 2009 ...
Страница 667: ......