Parameters
List of Parameters
1-264
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the speed/torque envelop curve for the load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
Dependency:
The following applies: p2182 < p2183 < p2184
Refer to: p2182, p2183, p2189, p2190
Refer to: A07926
Description:
Sets the speed/torque envelope curve for load monitoring.
Dependency:
The following applies: p2185 > p2186
Refer to: p2182, p2186
Refer to: A07926
Note:
The upper envelope curve is defined by p2185, p2187 and p2189.
Description:
Sets the speed/torque envelope curve for load monitoring.
Dependency:
The following applies: p2186 < p2185
Refer to: p2182, p2185
Refer to: A07926
Note:
The lower envelope curve is defined by p2186, p2188 and p2190.
Description:
Sets the speed/torque envelope curve for load monitoring.
Dependency:
The following applies: p2187 > p2188
Refer to: p2183, p2188
Refer to: A07926
Note:
The upper envelope curve is defined by p2185, p2187 and p2189.
p2184[0...n]
Load monitoring speed threshold value 3 / n_thresh 3
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [rpm]
210000.00 [rpm]
1500.00 [rpm]
p2185[0...n]
Load monitoring torque threshold 1, upper / M_thresh 1 upper
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [Nm]
20000000.00 [Nm]
10000000.00 [Nm]
p2186[0...n]
Load monitoring torque threshold 1, lower / M_thresh 1 lower
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [Nm]
20000000.00 [Nm]
0.00 [Nm]
p2187[0...n]
Load monitoring torque threshold 2, upper / M_thresh 2 upper
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [Nm]
20000000.00 [Nm]
10000000.00 [Nm]