List of Parameters
Parameters
1-287
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Selection of the response used to stop the motors when the OFF command is sent.
Re p2383 = 1:
OFF1, OFF2, or OFF3 disconnects the external motors from the line in the order 3 - 2 - 1. In the case of OFF2 and
OFF3, the main motor is disconnected immediately with the OFF command; in the case of OFF1, the main motor is
not disconnected until after all external motors have been disconnected. The time set in p2387 is applied as a wait
time between the disconnection of each motor.
Value:
0:
Normal stop
1:
Sequential stop
Caution:
If p2383 = 1 and the OFF1 command is pending, the main motor will not be stopped until all external motors have
been disconnected and time p2387 has elapsed. The disconnection of the external motors can also serve as a
means to re-accelerate the main motor.
Description:
Wait time once the staging conditions have been met until the external motor is switched on.
The activation of the corresponding status bit (p2379) for controlling the contactors or the motor starter is delayed
by this time, while the main motor falls back to the staging speed (p2378).
Description:
Time during which the staging speed (see p2378) of the main motor is maintained after an external motor has been
connected and the main motor has been decelerated to the staging speed.
Description:
Wait time once the destaging conditions have been met until the external motor is switched off.
The resetting of the corresponding status bit (r2379) for controlling the contactors or the motor starter is delayed by
this time, while the main motor ramps up to the staging speed (p2378).
Description:
Time during which the destaging speed (see p2378) of the main motor is maintained after an external motor has
been disconnected and the main motor has been accelerated to the destaging speed.
p2383
Staging stop mode / Staging stop mode
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 1 0
p2384
Staging motor ON delay / Staging t_del_ON
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.000 [s]
999.000 [s]
0.000 [s]
p2385
Staging speed hold time / Stag n_hold time
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.000 [s]
999.000 [s]
0.000 [s]
p2386
Staging motor OFF delay / Staging t_del_OFF
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.000 [s]
999.000 [s]
0.000 [s]
p2387
Destaging speed hold time / Destag t_hold
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.000 [s]
999.000 [s]
0.000 [s]