List of Parameters
Parameters
1-37
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the type of power unit found.
Value:
2:
MICROMASTER 440
3:
MICROMASTER 411
4:
MICROMASTER 410
5:
MICROMASTER 436
6:
MICROMASTER 440 PX
7:
MICROMASTER 430
100:
SINAMICS S
101:
SINAMICS S (value)
102:
SINAMICS S (combi)
112:
PM220 (SINAMICS G120)
113:
PM230 (SINAMICS G120)
114:
PM240 (SINAMICS G120)
115:
PM250 (SINAMICS G120)
116:
PM260 (SINAMICS G120)
118:
SINAMICS G120 Px
120:
PM340 (SINAMICS S120)
150:
SINAMICS G
200:
SINAMICS GM
250:
SINAMICS SM
260:
SINAMICS SM120
300:
SINAMICS GL
350:
SINAMICS SL
400:
SINAMICS DCM
Note:
For parallel circuit configurations, the parameter index is assigned to a power unit.
Description:
Displays the properties supported by the power unit hardware.
Description:
The duty cycles can be overloaded provided that the drive converter is operated with its base load current before
and after the overload. This is based on a load duty cycle of 300 s.
Value:
0:
Load duty cycle with high overload for vector drives
1:
Load duty cycle with low overload for vector drives
Notice:
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
Note:
When the parameter is changed, all of the motor parameters, the technological application and the control mode
are pre-assigned according to the selected application. The parameter has not influence when calculating the ther-
mal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
r0203[0...n]
Actual power unit type / PU actual type
Access level:
3
Calculated:
-
Data type:
Integer16
Unit:
-
Scaling:
-
Data set:
PDS
r0204[0...n]
Power unit hardware properties / PU HW property
Access level:
3
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
PDS
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
RFI filter available
Yes
No
-
07
F3E regenerative feedback into the line sup-
ply
Yes
No
-
08
Internal Braking Module
Yes
No
-
12
Safe Brake Control (SBC) supported
No
Yes
-
14
Internal LC output filter
Yes
No
-
p0205
Power unit application / PU application
PM230
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1, 2)
Scaling:
-
Data set:
-
Min Max Factory
setting
0 1 1
Содержание CU230P-2 CAN
Страница 1: ...s SINAMICS G120 Control Units CU230P 2 Parameter Manual 11 2009 SINAMICS ...
Страница 2: ......
Страница 666: ...Index C 666 Siemens AG 2009 All Rights Reserved SINAMICS G120 Control Units CU230P 2 Parameter Manual LH9 11 2009 ...
Страница 667: ......