Parameters
List of Parameters
1-342
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Display and connector output for the actual value after the limiter of the free technology controller 1.
Description:
Display and connector output for the system deviation of the free technology controller 1.
Description:
Sets the time constant for the differentiation (D component) of the free technology controller 1.
Note:
Value = 0: Differentiation is deactivated.
Description:
Sets the proportional gain (P component) of the free technology controller 1.
Note:
Value = 0: The proportional gain is deactivated.
Description:
Sets the integral time (I component, integrating time constant) of the free technology controller 1.
Note:
Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
Description:
Sets the maximum limit of the free technology controller 1.
Dependency:
Refer to: p11192
Note:
The maximum limit must always be greater than the minimum limit (p11191 > p11192).
Description:
Sets the minimum limit of the free technology controller 1.
Dependency:
Refer to: p11191
Note:
The maximum limit must always be greater than the minimum limit (p11191 > p11192).
r11172
CO: Free tec_ctrl 1 actual value after limiter / Ftec1 act v af lim
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-
r11173
CO: Free tec_ctrl 1 system deviation / Ftec1 sys dev
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-
p11174
Free tec_ctrl 1 differentiation time constant / Ftec1 D comp T
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.000 [s]
60.000 [s]
0.000 [s]
p11180
Free tec_ctrl 1 proportional gain / Ftec1 Kp
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.000 1000.000
1.000
p11185
Free tec_ctrl 1 integral time / Ftec1 Tn
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.000 [s]
10000.000 [s]
30.000 [s]
p11191
CO: Free tec_ctrl 1 limit maximum / Ftec1 lim max
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
-200.00 [%]
200.00 [%]
100.00 [%]
p11192
CO: Free tec_ctrl 1 limit minimum / Ftec1 lim min
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
-200.00 [%]
200.00 [%]
0.00 [%]