List of Parameters
Parameters
1-271
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the value for fixed value 11 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets the value for fixed value 12 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets the value for fixed value 13 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets the value for fixed value 14 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets the value for fixed value 15 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2211[0...n]
CO: Technology controller, fixed value 11 / Tec_ctrl fix val11
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
DDS, p0180
Min Max Factory
setting
-200.00 [%]
200.00 [%]
110.00 [%]
p2212[0...n]
CO: Technology controller, fixed value 12 / Tec_ctrl fix val12
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
DDS, p0180
Min Max Factory
setting
-200.00 [%]
200.00 [%]
120.00 [%]
p2213[0...n]
CO: Technology controller, fixed value 13 / Tec_ctrl fix val13
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
DDS, p0180
Min Max Factory
setting
-200.00 [%]
200.00 [%]
130.00 [%]
p2214[0...n]
CO: Technology controller, fixed value 14 / Tec_ctrl fix val14
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
DDS, p0180
Min Max Factory
setting
-200.00 [%]
200.00 [%]
140.00 [%]
p2215[0...n]
CO: Technology controller, fixed value 15 / Tec_ctrl fix val15
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
DDS, p0180
Min Max Factory
setting
-200.00 [%]
200.00 [%]
150.00 [%]