List of Faults and Alarms
Faults and Alarms
3-597
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
A01017
Component lists changed
Reaction:
NONE
Acknowledge:
NONE
Cause:
On the memory card, one file in the directory /SIEMENS/SINAMICS/DATA or /ADDON/SINAMICS/DATA has been
illegally changed with respect to that supplied from the factory. No changes are permitted in this directory.
Alarm value (r2124, interpret decimal):
The problem is indicated in the first digit of the alarm value:
1. File does not exist.
2. Firmware version of the file does not match the software version.
3. The file checksum is incorrect.
The second digit of the alarm value indicates in which directory the file is located:
0: Directory /SIEMENS/SINAMICS/DATA/
1. Directory /ADDON/SINAMICS/DATA/
The third digit of the alarm value indicates the file:
0: File MOTARM.ACX
1: File MOTSRM.ACX
2: File MOTSLM.ACX
3: File ENCDATA.ACX
4: File FILTDATA.ACX
5: File BRKDATA.ACX
6: File DAT_BEAR.ACX
7: File CFG_BEAR.ACX
Remedy:
For the memory card file involved, restore the status originally supplied from the factory.
F01018
Booting has been interrupted several times
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
Module booting was interrupted several times.
Possible reasons for booting being interrupted:
- POWER OFF of the module.
- CPU crash.
- USER data invalid.
After this fault is output, then the module is booted with the factory settings.
Remedy:
Power down the module and power it up again.
Note:
After switching on, the module reboots from the USER data (if available).
If the fault situation is repeated, then this fault is again output after several interrupted boots.
A01019
Writing to the removable data medium unsuccessful
Reaction:
NONE
Acknowledge:
NONE
Cause:
The write access to the removable data medium was unsuccessful.
Remedy:
Remove and check the removable data medium. Then run the data backup again.
F01023
Software timeout (internal)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An internal software timeout has occurred.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.