List of Parameters
Parameters
1-297
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Resets the number of activations of emergency operation and the number of faults which have occurred (in r3887).
0 = Do not reset
1 = Reset
Description:
Displays the status word for emergency operation (ESM).
Description:
Exits quick commissioning (p0010 = 1) with automatic calculation of all parameters of all existing drive data sets
that depend on the entries made during quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning.
The interconnections of PROFIBUS PZD telegram selection (p0922) and the interconnections via p0700, p1000
and p1500 are re-established and all of the dependent motor, open-loop and control-loop control parameters are
calculated (corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p0700, p1000 and p1500 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the calculations associated with the motor, open-loop and closed-loop control parameters
corresponding to p0340 = 1.
Value:
0:
No quick parameterization
1:
Quick parameterization after parameter reset
2:
Quick parameterization (only) for BICO and motor parameters
3:
Quick parameterization for motor parameters (only)
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of 0.
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters associ-
ated with a selected Siemens catalog motor are not overwritten.
If a catalog motor has not been selected (see p0300), then the following parameters are reset with p3900 > 0 in
order to restore the situation that applied when commissioning the drive for the first time:
for induction motors p0320, p0352, p0362 ... p0369, p0604, p0605, p0626 ... p0628.
for synchronous motors p0326, p0327, p0352, p0604, p0605.
p3888
ESM reset number of activations and faults / ESM reset act flts
Access level:
4
Calculated:
-
Data type:
Unsigned8
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 1 0
r3889.0...6
CO/BO: ESM status word / ESM status word
Access level:
3
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Emergency operation (ESM) active
Yes
No
-
01
Inversion of the direction of rotation
Yes
No
-
02
Setpoint signal lost
Yes
No
-
03
Technology controller actual value (p2264)
lost
Yes
No
-
04
Bypass active
Yes
No
-
05
ESM setpoint technology controller parame-
terized (p3884)
Yes
No
-
06
Technology controller active during emer-
gency operation
Yes
No
-
p3900
Completion of quick commissioning / Compl quick_comm
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1)
Scaling:
-
Data set:
-
Min Max Factory
setting
0 3 0