List of Parameters
Parameters
1-107
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the signal source to select the Command Data Set bit 1 (CDS bit 1).
Dependency:
Refer to: r0050, p0810, r0836
Note:
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
Description:
Copies one Drive Data Set (DDS) into another.
Index:
[0] = Source Drive Data Set
[1] = Target Drive Data Set
[2] = Start copying procedure
Note:
Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In Index 1, enter the drive data set data that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
Description:
Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency:
Refer to: r0051, p0826, r0837
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source to select the Drive Data Set, bit 1 (DDS, bit 1).
Dependency:
Refer to: r0051, r0837
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0811
BI: Command data set selection CDS bit 1 / CDS select., bit 1
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
- - 0
p0819[0...2]
Copy Drive Data Set DDS / Copy DDS
Access level:
2
Calculated:
-
Data type:
Unsigned8
Can be changed:
C(15)
Scaling:
-
Data set:
-
Min Max Factory
setting
0 3 0
p0820[0...n]
BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
C(15), T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 0
p0821[0...n]
BI: Drive Data Set selection DDS bit 1 / DDS select., bit 1
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
C(15), T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 0