List of Parameters
Parameters
1-125
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets a value for the fixed speed / velocity setpoint 6.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets a value for the fixed speed / velocity setpoint 7.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets a value for the fixed speed / velocity setpoint 8.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets a value for the fixed speed / velocity setpoint 9.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets a value for the fixed speed / velocity setpoint 10.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1006[0...n]
CO: Fixed speed setpoint 6 / n_set_fixed 6
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Data set:
DDS, p0180
Min Max Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1007[0...n]
CO: Fixed speed setpoint 7 / n_set_fixed 7
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Data set:
DDS, p0180
Min Max Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1008[0...n]
CO: Fixed speed setpoint 8 / n_set_fixed 8
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Data set:
DDS, p0180
Min Max Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1009[0...n]
CO: Fixed speed setpoint 9 / n_set_fixed 9
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Data set:
DDS, p0180
Min Max Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1010[0...n]
CO: Fixed speed setpoint 10 / n_set_fixed 10
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Data set:
DDS, p0180
Min Max Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]