List of Parameters
Parameters
1-121
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays those parameters with a value other than the factory setting for this drive.
Dependency:
Refer to: r0990, r0991
Note:
Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here.
This list completely comprises the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be
read from a higher-level control system (e.g. PROFIBUS master).
Description:
Sets the source for the speed setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value:
0:
No main setpoint
1:
Motorized potentiometer
2:
Analog setpoint
3:
Fixed speed setpoint
7:
Analog setpoint 2
10:
Motor potenti no main setpoint
11:
Motor potenti motor potentiometer
12:
Motor potenti analog setpoint
13:
Motor potenti fixed speed setpoint
17:
Motor potenti analog setpoint 2
20:
Analog se no main setpoint
21:
Analog se motor potentiometer
22:
Analog se analog setpoint
23:
Analog se fixed speed setpoint
27:
Analog se analog setpoint 2
30:
Fixed speed se no main setpoint
31:
Fixed speed se motor potentiometer
32:
Fixed speed se analog setpoint
33:
Fixed speed se fixed speed setpoint
37:
Fixed speed se analog setpoint 2
70:
Analog setpoint 2 + no main setpoint
71:
Analog setpoint 2 + motor potentiometer
72:
Analog setpoint 2 + analog setpoint
73:
Analog setpoint 2 + fixed speed setpoint
77:
Analog setpoint 2 + analog setpoint 2
Dependency:
When changing this parameter, the following settings are influenced:
Refer to: p1070, p1071, p1075, p1076
Caution:
If p1000 is selected as the main setpoint of the fieldbus, the following BICO interconnection is set automatically:
p2051[1] = r0063
Note:
With PROFIBUS/PROFINET Control Units, p0922 = 999 must be set so that the command or setpoint sources can
be changed.
r0999[0...99]
List of modified parameters 10 / List chang. par 10
Access level:
4
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
p1000[0...n]
Speed setpoint selection / n_set sel
CU230P-2 CAN
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
0 77
2