Parameters
List of Parameters
1-184
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the signal source for the scaling of the P gain of the speed controller. This also makes the effective P gain
(including adaptations) scalable.
Description:
Displays the effective P gain of the speed controller.
Description:
Displays the effective integral time of the speed controller.
Description:
Sets the P gain for encoderless operation for the speed controller.
Note:
The product p0341 * p0342 is taken into account when automatically calculating the speed controller (p0340 = 1, 3,
4).
Description:
Set the integral time for encoderless operation for the speed controller.
Description:
Sets the signal source to hold the integrator for the speed controller.
Description:
Sets the signal source to set the integrator setting value (p1478).
Dependency:
Refer to: p1478, p1479
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1466[0...n]
CI: Speed controller P-gain scaling / n_ctrl Kp scal
Access level:
4
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Data set:
CDS, p0170
Min Max Factory
setting
- - 1
r1468
CO: Speed controller P-gain effective / n_ctrl Kp eff
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
-
Scaling:
-
Data set:
-
r1469
Speed controller integral time effective / n_ctrl Tn eff
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[ms]
Scaling:
-
Data set:
-
p1470[0...n]
Speed controller encoderless operation P-gain / n_ctrl SLVC Kp
Access level:
2
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.000 999999.000
0.300
p1472[0...n]
Speed controller encoderless operation integral time / n_ctrl SLVC Tn
Access level:
2
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.0 [ms]
100000.0 [ms]
20.0 [ms]
p1476[0...n]
BI: Speed controller hold integrator / n_ctrl integ stop
Access level:
4
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 0
p1477[0...n]
BI: Speed controller set integrator value / n_ctrl integ set
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 0