List of Parameters
Parameters
1-293
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3111
Refer to: F07862
Description:
Displays the status of NAMUR signal bit bar.
The faults or alarms are assigned to the appropriate signaling/message classes and influence a specific message
bit.
Description:
Displays the fault value of the oldest active fault.
Description:
Sets the signal source for the speed actual value of the load monitoring.
Dependency:
Refer to: r2169, p2181, p2192, p2193, p3231
Refer to: A07920, A07921, A07922, F07923, F07924, F07925
Note:
The parameter is only effective for p2193 = 2.
p3112[0...n]
BI: External fault 3 enable negated / Ext flt 3 enab neg
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 0
r3113.0...15
CO/BO: NAMUR message bit bar / NAMUR bit bar
Access level:
3
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fault drive converter data electronics / soft-
ware error
Yes
No
-
01
Line supply fault
Yes
No
-
02
DC link overvoltage
Yes
No
-
03
Fault drive converter power electronics
Yes
No
-
04
Drive converter overtemperature
Yes
No
-
05
Ground fault
Yes
No
-
06
Motor overload
Yes
No
-
07
Bus error
Yes
No
-
08
External safety-relevant shutdown
Yes
No
-
10
Error internal communications
Yes
No
-
11
Infeed fault
Yes
No
-
15
Other faults
Yes
No
-
r3131
CO: Current fault value / Current flt value
Access level:
3
Calculated:
-
Data type:
Integer32
Unit:
-
Scaling:
-
Data set:
-
p3230[0...n]
CI: Load monitoring, speed actual value / Load monit n_act
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Data set:
CDS, p0170
Min Max Factory
setting
- - 0