Parameters
List of Parameters
1-198
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the smoothing time for the flux setpoint in the field-weakening range
Note:
Only the flux setpoint rise is smoothed
Description:
Displays the pre-control value for the field weakening current.
Description:
Displays the output of the field weakening controller (synchronous motor).
Index:
[0] = PI output
[1] = I output
Description:
Sets the P gain of the field-weakening controller.
Description:
Sets the integral-action time of the field-weakening controller.
Description:
Displays the output of the field weakening controller. The value is referred to the rated motor flux.
Description:
Displays the effective flux setpoint.
The value is referred to the rated motor flux.
p1584[0...n]
Field weakening operation, flux setpoint smoothing time / Field weak T_smth
Access level:
4
Calculated:
p0340 = 1,3
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0 [ms]
20000 [ms]
0 [ms]
r1589
Field-weakening current, pre-control value / FieldWkCurrPrectrl
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Arms]
Scaling:
p2002
Data set:
-
r1593[0...1]
CO: Field weakening controller / flux controller output / Field/Fl_ctrl outp
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Arms]
Scaling:
p2002
Data set:
-
p1594[0...n]
Field-weakening controller, P gain / Field_ctrl Kp
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 1000.00
0.00
p1596[0...n]
Field weakening controller integral-action time / Field_ctrl Tn
PM230
PM240
PM250, PM260
Access level:
3
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
10 [ms]
10000 [ms]
300 [ms]
r1597
CO: Field weakening controller output / Field_ctrl output
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-
r1598
CO: Total flux setpoint / Flux setp total
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-