List of Parameters
Parameters
1-187
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the scaling for the acceleration pre-control of the speed/velocity controller.
Dependency:
When the reference model is activated (p1400.3 = 1) and for an internal acceleration pre-control (p1400.2 = 0), the
acceleration pre-control is switched out (disabled). The reference model (p1400.3 = 1) and external acceleration
pre-control (p1400.2 = 1) can be operated together.
Refer to: p0341, p0342
Note:
The parameter is set to 100% by the rotating measurement (refer to p1960).
The acceleration pre-control may not be used if the speed setpoint manifests significant ripple (e.g. analog setpoint)
and the rounding-off in the speed ramp-function generator is disabled.
We also recommend that the pre-control mode is not used if there is gearbox backlash.
Description:
Sets the scaling for the acceleration integrator at low speeds (only for encoderless torque control).
Dependency:
Refer to: p0341, p0342
Description:
Sets the source for the torque setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value:
0:
No main setpoint
2:
Analog setpoint
7:
Analog setpoint 2
20:
Analog se no main setpoint
22:
Analog se analog setpoint
27:
Analog se analog setpoint 2
70:
Analog setpoint 2 + no main setpoint
72:
Analog setpoint 2 + analog setpoint
77:
Analog setpoint 2 + analog setpoint 2
Dependency:
When changing this parameter, the following settings are influenced:
Refer to: p1503, p1511
Note:
With PROFIBUS / PROFINET Control Units, p0922 = 999 must be set so that the command and setpoint sources
can be changed.
p1496[0...n]
Acceleration pre-control scaling / a_before scaling
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.0 [%]
10000.0 [%]
0.0 [%]
p1499[0...n]
Accelerating for torque control, scaling / a for M_ctrl scal
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.0 [%]
400.0 [%]
100.0 [%]
p1500[0...n]
Torque setpoint selection / M_set sel
CU230P-2 CAN
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
0 77
0