List of Parameters
Parameters
1-347
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the ramp-up and ramp-down time for the maximum and minimum limit (p11191, p11192) of the free technol-
ogy controller 2.
Dependency:
Refer to: p11291, p11292
Note:
The ramp-up/ramp-down times are referred to 100%.
Description:
Display and connector output for the output signal of the free technology controller 2.
Description:
Sets the signal source for the maximum limit of the free technology controller 2.
Dependency:
Refer to: p11291
Description:
Sets the signal source for the minimum limit of the free technology controller 2.
Dependency:
Refer to: p11292
Description:
Sets the signal source for the limit offset of the free technology controller 2.
p11293
Free tec_ctrl 2 limit ramp-up/ramp-down time / Ftec2 lim r-u/r-dn
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [s]
100.00 [s]
1.00 [s]
r11294
CO: Free tec_ctrl 2 output signal / Ftec2 out_sig
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-
p11297
CI: Free tec_ctrl 2 limit maximum signal source / Ftec2 lim max s_s
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
- - 11291[0]
p11298
CI: Free tec_ctrl 2 limit minimum signal source / Ftec2 lim min s_s
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
- - 11292[0]
p11299
CI: Free tec_ctrl 2 limit offset signal source / Ftec2 lim offs
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
- - 0