List of Parameters
Parameters
1-337
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the ramp-down time for the free technology controller 0.
Dependency:
Refer to: p11057
Note:
The ramp-down time is referred to 100 %.
Description:
Display and connector output for the setpoint after the ramp-function generator of the free technology controller 0.
Description:
Sets the signal source for the actual value of the free technology controller 0.
Description:
Sets the smoothing time constant (PT1) for the actual value of the free technology controller 0.
Description:
Sets the upper limit for the actual value signal of the free technology controller 0.
Dependency:
Refer to: p11064
Description:
Sets the lower limit for the actual value signal of the free technology controller 0.
Dependency:
Refer to: p11064
Description:
Sets the inversion of the actual value signal of the free technology controller 0.
Value:
0:
No inversion
1:
Inversion
p11058
Free tec_ctrl 0 setpoint ramp-down time / Ftec0 setp t_r-dn
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [s]
650.00 [s]
1.00 [s]
r11060
CO: Free tec_ctrl 0 setpoint after ramp-function generator / Ftec0 setp aft RFG
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-
p11064
CI: Free tec_ctrl 0 actual value signal source / Ftec0 act v s_s
Access level:
2
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
- - 0
p11065
Free tec_ctrl 0 actual value smoothing time constant / Ftec0 act v T
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [s]
60.00 [s]
0.00 [s]
p11067
Free tec_ctrl 0 actual value upper limit / Ftec0 act v up lim
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
-200.00 [%]
200.00 [%]
100.00 [%]
p11068
Free tec_ctrl 0 actual value lower limit / Ftec0 act v lo lim
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
-200.00 [%]
200.00 [%]
-100.00 [%]
p11071
Free tec_ctrl 0 actual value inversion / Ftec0 act v inv
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 1 0