Parameters
List of Parameters
1-38
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
The duty cycles can be overloaded provided that the drive converter is operated with its base load current before
and after the overload. This is based on a load duty cycle of 300 s.
Value:
0:
Load duty cycle with high overload for vector drives
1:
Load duty cycle with low overload for vector drives
Notice:
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
Note:
When the parameter is changed, all of the motor parameters, the technological application and the control mode
are pre-assigned according to the selected application. The parameter has not influence when calculating the ther-
mal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
Description:
Displays the rated power unit power for various load duty cycles.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = Reserved
[4] = Reserved
Dependency:
IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
Refer to: p0100, p0205
Description:
Displays the rated power unit power for various load duty cycles.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = Reserved
[4] = Reserved
Dependency:
Refer to: p0205
Description:
Displays the rated line supply voltage of the power unit.
r0208 = 400 : 380 - 480 V +/-10 %
r0208 = 500 : 500 - 600 V +/-10 %
r0208 = 690 : 660 - 690 V +/-10 %
p0205
Power unit application / PU application
PM240
PM250, PM260
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1, 2)
Scaling:
-
Data set:
-
Min Max Factory
setting
0 1 0
r0206[0...4]
Rated power unit power / PU P_rated
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[kW]
Scaling:
-
Data set:
-
r0207[0...4]
Rated power unit current / PU PI_rated
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Arms]
Scaling:
-
Data set:
-
r0208
Rated power unit line supply voltage / PU V_rated
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Vrms]
Scaling:
-
Data set:
-