Parameters
List of Parameters
1-134
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the speed limit/velocity limit effective in the setpoint channel.
Dependency:
Refer to: p1082, p1083, p1085, p1086, p1088
Description:
Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency:
Refer to: p1071, r1073, r1078
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency:
Refer to: p1071, r1073, r1078
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for scaling the main setpoint.
Description:
Displays the effective main setpoint. The value shown is the main setpoint after scaling.
Description:
Sets the signal source for the supplementary setpoint.
Dependency:
Refer to: p1076, r1077, r1078
p1063[0...n]
Speed limit setpoint channel / n_limit setp
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.000 [rpm]
210000.000 [rpm]
210000.000 [rpm]
p1070[0...n]
CI: Main setpoint / Main setpoint
CU230P-2 CAN
CU230P-2 HVAC
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Data set:
CDS, p0170
Min Max Factory
setting
- - 755[0]
p1070[0...n]
CI: Main setpoint / Main setpoint
CU230P-2 DP
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Data set:
CDS, p0170
Min Max Factory
setting
- - 2050[1]
p1071[0...n]
CI: Main setpoint scaling / Main setp scal
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Data set:
CDS, p0170
Min Max Factory
setting
- - 1
r1073
CO: Main setpoint effective / Main setpoint eff
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[rpm]
Scaling:
p2000
Data set:
-
p1075[0...n]
CI: Supplementary setpoint / Suppl setpoint
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Data set:
CDS, p0170
Min Max Factory
setting
- - 0