List of Parameters
Parameters
1-345
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the ramp-down time of the free technology controller 2.
Dependency:
Refer to: p11257
Note:
The ramp-down time is referred to 100%.
Description:
Display and connector output for the setpoint after the ramp-function generator of the free technology controller 2.
Description:
Sets the signal source for the actual value of the free technology controller 2.
Description:
Sets the smoothing time constant (PT1) for the actual value of the free technology controller 2.
Description:
Sets the upper limit for the actual value signal of the free technology controller 2.
Dependency:
Refer to: p11264
Description:
Sets the lower limit for the actual value signal of the free technology controller 2.
Dependency:
Refer to: p11264
Description:
Sets the inversion of the actual value signal of the free technology controller 2.
Value:
0:
No inversion
1:
Inversion
p11258
Free tec_ctrl 2 setpoint ramp-down time / Ftec2 setp t_r-dn
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [s]
650.00 [s]
1.00 [s]
r11260
CO: Free tec_ctrl 2 setpoint after ramp-function generator / Ftec2 setp aft RFG
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-
p11264
CI: Free tec_ctrl 2 actual value signal source / Ftec2 act v s_s
Access level:
2
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
- - 0
p11265
Free tec_ctrl 2 actual value smoothing time constant / Ftec2 act v T
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [s]
60.00 [s]
0.00 [s]
p11267
Free tec_ctrl 2 actual value upper limit / Ftec2 act v up lim
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
-200.00 [%]
200.00 [%]
100.00 [%]
p11268
Free tec_ctrl 2 actual value lower limit / Ftec2 act v lo lim
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
-200.00 [%]
200.00 [%]
-100.00 [%]
p11271
Free tec_ctrl 2 actual value inversion / Ftec2 act v inv
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 1 0