526
14 TROUBLESHOOTING
14.4 List of Warning Codes
09A7H
Positioning
start signal
input at quick
external start
Positioning start signal has been input when 0: Start with
external command is set in [Pr.42] External command function
selection and 1: External command valid is set in [Cd.8]
External command valid.
[Operation of when the warning has occurred]
The positioning does not start.
Do not input Positioning start signal.
09A8H
Pre-analysis
not possible
The value other than 1 to 600 has been set in [Cd.3]
Positioning start No. during positioning data analysis in pre-
analysis mode.
[Operation of when the warning has occurred]
After the start trigger is input, the same operation in normal
analysis mode is started while the state remains in pre-
analysis mode.
Set a value within 1 to 600 in [Cd.3] Positioning start No.
09A9H
The axis to be interpolated is not in pre-analysis mode during
positioning data analysis in pre-analysis mode.
[Operation of when the warning has occurred]
After the start trigger is input, the same operation in normal
analysis mode is started while the state remains in pre-
analysis mode.
Change the state of the axis to be interpolated to pre-analysis
mode as well.
0A10H
Outside
command
speed range
The speed set in [Da.8] Command speed is over the speed
set in [Pr.8] Speed limit value.
[Operation of when the warning has occurred]
• [Da.8] Command speed is controlled with [Pr.8] Speed limit
value.
• In speed limit flag is on.
• Correct a value in [Da.8] Command speed within the setting
range. For details, refer to
• Correct the set value in the [Cd.13] Positioning operation
speed override. For details, refer to
Positioning operation speed override.
09F0H
No operation
termination
setting
The 50th point of block start data is set to Continue when the
positioning has been performed with block start data.
[Operation of when the warning has occurred]
The operation ends.
Set the 50th point of block start data to End.
09F1H
FOR to NEXT
nest
construction
FOR to NEXT is nested.
[Operation of when the warning has occurred]
The operation is continued.
Do not configure FOR to NEXT nest construction.
0B00H
Extension
parameter
acquisition
error
Extension parameters have not been acquired. (no file)
[Operation of when the warning has occurred]
The setting values of extension parameters of buffer memory
become as follows.
• Power on: Factory default setting value
• RUN: Setting value just before RUN
Write extension parameters to the storage location set in the
extension parameter storage setting, and change the CPU
module status from STOP to RUN.
0B01H
Extension parameters have not been acquired. (data error)
[Operation of when the warning has occurred]
The setting values of extension parameters of buffer memory
become factory default setting values.
Write extension parameters to the storage location set in the
extension parameter storage setting, and change the CPU
module status from STOP to RUN.
0B02H
Extension parameters have not been acquired. (retry count
over)
[Operation of when the warning has occurred]
The setting values of extension parameters of buffer memory
become factory default setting values.
• Change the CPU module status from STOP to RUN.
• Set Positioning module in the extension parameter storage
setting.
Warning
code
Warning
name
Cause and description
Action
Содержание MELSEC iQ-R RD75P4
Страница 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Страница 2: ......
Страница 13: ...11 MEMO ...
Страница 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Страница 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Страница 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Страница 511: ...13 PROGRAMMING 13 4 Program Example 509 13 Torque change program Step operation program Skip program ...
Страница 512: ...510 13 PROGRAMMING 13 4 Program Example Teaching program Continuous operation interrupt program ...
Страница 513: ...13 PROGRAMMING 13 4 Program Example 511 13 Target position change program Absolute position restoration program ...
Страница 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Страница 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Страница 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Страница 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Страница 568: ...566 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Common program ...
Страница 584: ...582 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Restart program ...
Страница 587: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 585 A Stop program ...
Страница 597: ......