12 DATA USED FOR POSITIONING CONTROL
12.11 Basic Parameter 3
487
12
12.11
Basic Parameter 3
This section describes the basic parameter 3 of the RD75. The start time and the storage location of module extension
parameters of the RD75 can be changed with the basic parameter 3. The basic parameter 3 can be changed only from
"Module Parameter" of the engineering tool.
For the setting method, refer to the following.
Operation mode
Switch the mode of the start time between the Q series-compatible mode and quick start mode. The setting is the same for all
the axes.
■
Default value
The default value is Q series-compatible mode.
Extended parameter storage setting
Set the storage location for module extension parameters. The setting is the same for all the axes.
By setting the extension parameter storage setting to "Positioning module", MELSEC-Q series programs that
extension parameters can be changed by turning on SM402, not by turning on Module access flag [X01] can
be utilized.
Operation mode
Description
Q series-compatible mode
The start time is 1.5ms. In this mode, the start time corresponds to the start time of the QD75N and LD75.
Quick start mode
The start time is 0.3ms.
Extended parameter storage setting
Description
CPU
The module extension parameters stored in the CPU module are used.
• When the power is turned on or the CPU module status is changed from STOP to RUN, the module
extension parameters in the module extension parameter file stored in the CPU module are reflected to
the buffer memory.
• At the module data backup or module data initialization, the parameters are reflected to the module
extension parameter file stored in the CPU module.
Positioning module
The module extension parameters stored in the RD75 are used.
• When the power is turned on, the module extension parameters in the module extension parameter file
stored in the the RD75 are reflected to the buffer memory. When the CPU module status is changed from
STOP to RUN, the value just before the status change is held.
• At the module data backup or module data initialization, the parameters are reflected to the module
extension parameter file stored in the RD75.
Содержание MELSEC iQ-R RD75P4
Страница 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Страница 2: ......
Страница 13: ...11 MEMO ...
Страница 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Страница 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Страница 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Страница 511: ...13 PROGRAMMING 13 4 Program Example 509 13 Torque change program Step operation program Skip program ...
Страница 512: ...510 13 PROGRAMMING 13 4 Program Example Teaching program Continuous operation interrupt program ...
Страница 513: ...13 PROGRAMMING 13 4 Program Example 511 13 Target position change program Absolute position restoration program ...
Страница 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Страница 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Страница 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Страница 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Страница 568: ...566 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Common program ...
Страница 584: ...582 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Restart program ...
Страница 587: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 585 A Stop program ...
Страница 597: ......