314
8 COMMON FUNCTIONS
8.7 Amplifier-less Operation Function
Operation mode switching procedure
■
Switching from the normal operation mode to the amplifier-less operation mode
1.
Stop all operating axes, and check that BUSY signals of all axes are off.
2.
Turn off PLC READY signal [Y0].
3.
Check that RD75 READY signal [X0] is off.
4.
Set "ABCDH" in "[Cd.137] Amplifier-less operation mode switching request".
5.
Check that "[Md.70] Amplifier-less operation mode status" is set to "1: In amplifier-less operation mode".
■
Switching from the amplifier-less operation mode to the normal operation mode
1.
Stop all operating axes, and check that BUSY signals of all axes are off.
2.
Turn off PLC READY signal [Y0].
3.
Check that RD75 READY signal [X0] is off.
4.
Set "0000H" in "[Cd.137] Amplifier-less operation mode switching request".
5.
Check that "[Md.70] Amplifier-less operation mode status" is set to "0: In normal operation mode".
■
Operation chart
The following chart shows switching operation between the normal operation mode and the amplifier-less operation mode.
• Check that all input signals [X0 to X17] other than Module access flag [X1] are off, and switch the operation
mode between the normal operation mode and the amplifier-less operation mode. If the operation mode is
switched while any of input signals other than Module access flag [X1] in on, Error at switching from normal
operation mode to amplifier-less operation mode (Error code: 18B0H) or Error at switching from amplifier-
less operation mode to normal operation mode (Error code: 18B1H) occurs and the operation mode is not
switched.
• The switching operation is enabled when "0000H" or "ABCDH" is set in "[Cd.137] Amplifier-less operation
mode switching request". If a value other than "0000H" or "ABCDH" is set, the operation mode is not
switched and error detection is not performed.
• The operation mode is switched to the amplifier-less operation mode only when "[Cd.137] Amplifier-less
operation mode switching request" is set to "ABCDH" from "0000H". The operation mode is switched to the
normal operation mode only when "[Cd.137] Amplifier-less operation mode switching request" is set to
"0000H" from "ABCDH".
t
v
Cd.137
Md.70
0000H
0000H
ABCDH
0
0
1
Various operations
BUSY signal
[XC, XD, XE, XF]
RD75 READY signal [X0]
PLC READY signal [Y0]
Amplifier-less
operation mode
switching request
Amplifier-less
operation mode status
Normal operation
mode
Amplifier-less operation mode
Normal operation
mode
Содержание MELSEC iQ-R RD75P4
Страница 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Страница 2: ......
Страница 13: ...11 MEMO ...
Страница 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Страница 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Страница 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Страница 511: ...13 PROGRAMMING 13 4 Program Example 509 13 Torque change program Step operation program Skip program ...
Страница 512: ...510 13 PROGRAMMING 13 4 Program Example Teaching program Continuous operation interrupt program ...
Страница 513: ...13 PROGRAMMING 13 4 Program Example 511 13 Target position change program Absolute position restoration program ...
Страница 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Страница 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Страница 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Страница 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Страница 568: ...566 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Common program ...
Страница 584: ...582 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Restart program ...
Страница 587: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 585 A Stop program ...
Страница 597: ......