14 TROUBLESHOOTING
14.5 List of Error Codes
1B03H
OPR speed
error
A value outside the setting range is set in [Pr.46] OPR speed
of OPR basic parameter.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
1B04H
A value set in [Pr.46] OPR speed of OPR basic parameter is
over [Pr.8] Speed limit value.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value so that [Pr.46] OPR speed is equal to or
below [Pr.8] Speed limit value, and turn on PLC READY signal
[Y0].
For details, refer to the following.
Page 389 [Pr.8] Speed limit value
1B05H
A value set in [Pr.46] OPR speed of OPR basic parameter is
below [Pr.7] Bias speed at start.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value so that [Pr.46] OPR speed is equal to or
over [Pr.7] Bias speed at start, and turn on PLC READY
signal [Y0].
For details, refer to the following.
Page 386 [Pr.7] Bias speed at start
1B06H
Creep speed
error
A value outside the setting range is set in [Pr.47] Creep speed
of OPR basic parameter.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
1B07H
A value set in [Pr.47] Creep speed of OPR basic parameter is
over [Pr.46] OPR speed.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value so that [Pr.47] Creep speed is equal to or
below [Pr.46] OPR speed, and turn on PLC READY signal
[Y0].
For details, refer to the following.
1B08H
A value set in [Pr.47] Creep speed of OPR basic parameter is
below [Pr.7] Bias speed at start.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value so that [Pr.47] Creep speed is equal to or
over [Pr.7] Bias speed at start, and turn on PLC READY
signal [Y0].
For details, refer to the following.
Page 386 [Pr.7] Bias speed at start
1B09H
OPR retry error
A value outside the setting range is set in [Pr.48] OPR retry of
OPR basic parameter.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
1B0AH
Setting for the
movement
amount after
near-point dog
ON error
A value outside the setting range is set in [Pr.50] Setting for
the movement amount after near-point dog ON of OPR
detailed parameter.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
Setting for the movement amount after near-point dog ON.
1B0BH
OPR
acceleration
time selection
error
A value outside the setting range is set in [Pr.51] OPR
acceleration time selection of OPR detailed parameter.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
OPR acceleration time selection.
1B0CH
OPR
deceleration
time selection
error
A value outside the setting range is set in [Pr.52] OPR
deceleration time selection of OPR detailed parameter.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
OPR deceleration time selection.
1B0DH
OPR torque limit
value error
A value outside the setting range is set in [Pr.54] OPR torque
limit value of OPR detailed parameter.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
1B0EH
[Pr.54] OPR torque limit value of OPR detailed parameter is
over [Pr.17] Torque limit setting value of detailed parameter 1.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0].
For details, refer to the following.
Page 394 [Pr.17] Torque limit setting value
Page 418 [Pr.54] OPR torque limit value
1B0FH
Deviation
counter clear
signal output
time setting
error
A value outside the setting range is set in [Pr.55] Deviation
counter clear signal output time of OPR detailed parameter.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
Deviation counter clear signal output time.
Error
code
Error name
Cause and description
Action
Содержание MELSEC iQ-R RD75P4
Страница 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Страница 2: ......
Страница 13: ...11 MEMO ...
Страница 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Страница 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Страница 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Страница 511: ...13 PROGRAMMING 13 4 Program Example 509 13 Torque change program Step operation program Skip program ...
Страница 512: ...510 13 PROGRAMMING 13 4 Program Example Teaching program Continuous operation interrupt program ...
Страница 513: ...13 PROGRAMMING 13 4 Program Example 511 13 Target position change program Absolute position restoration program ...
Страница 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Страница 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Страница 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Страница 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Страница 568: ...566 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Common program ...
Страница 584: ...582 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Restart program ...
Страница 587: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 585 A Stop program ...
Страница 597: ......