5 MANUAL CONTROL
5.4 Manual Pulse Generator Operation
195
5
Operation timing and the processing time
The following shows the details on the operation timing and processing time in the manual pulse generator operation.
Normal timing time
Position control by the manual pulse generator operation
In the manual pulse generator operation, the position is moved for Manual pulse generator 1 pulse movement amount per
pulse. The current feed value in the positioning control by the manual pulse generator operation can be calculated using the
following calculation formula.
Current feed value = Number of input pulses
[Cd.20] Manual pulse generator 1 pulse input magnification
Manual pulse
generator 1 pulse movement amount
For example, when [Pr.1] Unit setting is mm and [Cd.20] Manual pulse generator 1 pulse input magnification is 2, 100 pulses
are input from the manual pulse generator and the current feed value is as follows.
100
2
0.1 = 20 (
m)
= 200 (Current feed value)
The number of pulses output actually to the drive unit is (Manual pulse generator 1 pulse movement amount/Movement
amount per pulse).
The movement amount per pulse is given by the following calculation formula.
For example, when [Pr.1] Unit setting is mm and the movement amount per pulse is 1
m, 0.1/1 = 1/10, that is, the number of
pulses output to the drive unit from the manual pulse generator per pulse is 1/10 pulse. Thus, the RD75 outputs 1 pulse to the
drive unit after receiving 10 pulses from the manual pulse generator.
t1
t2
t3
t4
0 to 0.88ms
1.7 to 30.2ms
58.6 to 87.6ms
0 to 0.88ms
[Pr.1] Unit setting
mm
inch
degree
pulse
Manual pulse generator 1 pulse
movement amount
0.1
m
0.00001inch
0.00001 degree
1 pulse
Item
Symbol
[Pr.2] No. of pulses per rotation
Ap
[Pr.3] Movement amount per rotation
Al
[Pr.4] Unit magnification
Am
Movement amount per pulse
A
t1
t3
t4
t2
0
0
1
Cd.21
Md.26
Manual pulse generator input pulse
Manual pulse generator
enable flag
BUSY signal
[XC, XD, XE, XF]
Start complete signal
[X10, X11, X12, X13]
Axis operation status
Pulse output to an external source
(PULSE)
Positioning operation
Standby
Manual pulse generator operation
Standby
Start complete signal does not turn on in the manual pulse generator operation.
Movement amount per pulse (A) =
Al × Am
Ap
Содержание MELSEC iQ-R RD75P4
Страница 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Страница 2: ......
Страница 13: ...11 MEMO ...
Страница 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Страница 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Страница 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Страница 511: ...13 PROGRAMMING 13 4 Program Example 509 13 Torque change program Step operation program Skip program ...
Страница 512: ...510 13 PROGRAMMING 13 4 Program Example Teaching program Continuous operation interrupt program ...
Страница 513: ...13 PROGRAMMING 13 4 Program Example 511 13 Target position change program Absolute position restoration program ...
Страница 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Страница 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Страница 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Страница 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Страница 568: ...566 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Common program ...
Страница 584: ...582 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Restart program ...
Страница 587: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 585 A Stop program ...
Страница 597: ......