12 DATA USED FOR POSITIONING CONTROL
12.3 Basic Setting
409
12
OPR basic parameter
[Pr.43] OPR method
Set OPR method for performing the machine OPR.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Default value
The default value is 0: Near-point dog method for all the axes.
OPR method
Setting
value
Description
Reference
Near-point dog method
0
After the speed of the OPR is decelerated when the near-point dog is on, the OPR stops
when the zero signal is detected and the machine OPR completes.
Stopper method 1
1
After the speed of the OPR is decelerated when the near-point dog is on, the OPR stops
with the stopper and the OPR completes when the dwell time is elapsed.
Stopper method 2
2
After the speed of the OPR is decelerated when the near-point dog is on, the OPR stops
with the stopper and the machine OPR completes when the zero signal is detected.
Stopper method 3
3
After the OPR starts at the creep speed, the OPR stops with the stopper and the machine
OPR completes when the zero signal is detected.
Count method 1
4
After the speed of the OPR is decelerated when the near-point dog is on, the OPR stops
when the zero signal is detected after the workpiece is moved for the specified distance,
and the machine OPR completes.
Count method 2
5
After the speed of the OPR is decelerated when the near-point dog is on, the workpiece is
moved for the specified distance and the machine OPR completes.
Data setting method
6
The position where the machine OPR starts is set as the OP, and the machine OPR
completes.
Buffer memory name
Axis 1
Axis 2
Axis 3
Axis 4
[Pr.43] OPR method
70
220
370
520
Содержание MELSEC iQ-R RD75P4
Страница 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Страница 2: ......
Страница 13: ...11 MEMO ...
Страница 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Страница 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Страница 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Страница 511: ...13 PROGRAMMING 13 4 Program Example 509 13 Torque change program Step operation program Skip program ...
Страница 512: ...510 13 PROGRAMMING 13 4 Program Example Teaching program Continuous operation interrupt program ...
Страница 513: ...13 PROGRAMMING 13 4 Program Example 511 13 Target position change program Absolute position restoration program ...
Страница 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Страница 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Страница 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Страница 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Страница 568: ...566 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Common program ...
Страница 584: ...582 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Restart program ...
Страница 587: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 585 A Stop program ...
Страница 597: ......