24
1 STARTING AND STOPPING
1.1 Starting
Quick start
Positioning controls can be started quickly by analyzing in advance the positioning data executed immediately after the
current operation to prevent the analysis time affecting the start. Positioning data for the major positioning controls can be
started in this mode.
By using an external command signal as a start trigger, positioning controls can be started bypassing a
program, which means that the operation is quickly started without being affected by the execution time of the
program.
Starting method
After setting positioning data, set [Cd.43] Analysis mode setting to 1: Pre-analysis mode and input a start trigger signal while
[Md.61] Analysis complete flag is 1: Analysis completed. The following table shows the start triggers used in this mode.
Depending on the start timing of the positioning data analysis, a start trigger used is determined. Even if the settings are
changed after the start of the positioning data analysis, the changed settings are not valid. Therefore, when the following
settings are configured, an external command signal (CHG) is used as a start trigger.
• [Pr.42] External command function selection is set to 0: Start with external command.
• [Cd.8] External command valid is set to 1: External command valid.
Otherwise, Positioning start signal [Y10, Y11, Y12, Y13] can be used as a start trigger.
Start trigger name
Starting method (Start trigger)
Positioning data to be started
Positioning start signal
Turning off and on Positioning start signal [Y10, Y11, Y12,
Y13]
Starts the positioning data specified in [Cd.3] Positioning start No.
External command
signal
Turning off and on an external command signal (CHG)
Starts the positioning data specified in [Cd.3] Positioning start No.
Содержание MELSEC iQ-R RD75P4
Страница 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Страница 2: ......
Страница 13: ...11 MEMO ...
Страница 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Страница 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Страница 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Страница 511: ...13 PROGRAMMING 13 4 Program Example 509 13 Torque change program Step operation program Skip program ...
Страница 512: ...510 13 PROGRAMMING 13 4 Program Example Teaching program Continuous operation interrupt program ...
Страница 513: ...13 PROGRAMMING 13 4 Program Example 511 13 Target position change program Absolute position restoration program ...
Страница 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Страница 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Страница 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Страница 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Страница 568: ...566 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Common program ...
Страница 584: ...582 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Restart program ...
Страница 587: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 585 A Stop program ...
Страница 597: ......