![ABB ACS380 Series Скачать руководство пользователя страница 99](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560099.webp)
Program features 99
Motor temperature measurement through the standard I/O
This section describes the temperature measurement of one motor when the drive
I/O terminals are used as the connection interface.
Motor temperature can be measured using Pt100 or PTC sensors connected to
analog input and output.
Warning!
According to IEC 60664, the connection of the motor
temperature sensor requires double or reinforced insulation between
motor live parts and the sensor. Reinforced insulation entails a clearance
and creepage distance of 8 mm (0.3 in) (400/500 V AC equipment).
If the assembly does not fulfill the requirement, the I/O board terminals must be
protected against contact and they may not be connected to other equipment, or the
temperature sensor must be isolated from the I/O terminals.
Temperature monitoring using Pt100 sensors
1…3 Pt100 sensors can be connected in series to an analog input and an analog
output.
The analog output feeds a constant excitation current of 9.1 mA through the sensor.
The sensor resistance increases as the motor temperature rises, as does the voltage
over the sensor. The temperature measurement function reads the voltage through
the analog input and converts it into degrees Celsius.
It is possible to adjust the motor temperature supervision limits and select how the
drive reacts when overtemperature is detected.
For the wiring of the sensor, see chapter
Electrical installation, AI1 and AI2 as Pt100,
Pt1000, Ni1000, KTY83 and KTY84 sensor inputs (X1)
in the
Hardware manual
of the
drive.
AI1
GND
One sensor
AO
GND
AI1
GND
AO
GND
Three sensors
Motor
3.3 nF
Motor
3.3 nF
ACS380 FW.book Page 99 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |
www.ghv.de