136 Parameters
11.03
DIO force selection
Selects the digital inputs, states which will be controlled by
parameter
11.04
. A bit in parameter
11.04
is provided for
each digital input, and its value is applied whenever the
corresponding bit in this parameter is 1.
0000h
0000h...FFFFh
Forced selections of digital inputs/outputs.
1=1
11.04
DIO force data
Defines the forced values for the digital inputs selected by
parameter
11.03 DIO force selection
. It is only possible to
force an input that has been selected in parameter
10.03
DI force selection
.
Bit 0 is the forced value for DIO1.
0000h
0000h...FFFFh
Forced values of digital inputs/outputs.
1=1
11.05
DIO1 configuration
Selects whether DIO1 is used as a digital output, digital
input, or frequency output.
Note
: DIOs cannot be used as frequency inputs.
Input
Digital output
DIO1 is used as a digital output.
0
Input
Digital input.
1
Frequency output
DIO1 is used as frequency output.
2
11.06
DIO1 output source
Selects a drive signal to be connected to digital
input/output DIO1 when it is configured to digital output by
parameter
11.05
.
Not
energized
Not energized
Output is not energized.
0
Energized
Output is energized.
1
Ready run
Bit 1 of
06.11
Main status word
. 2
Enabled
Bit 0 of
06.16
Drive status word 1
.
4
Started
Bit 5 of
06.16
Drive status word 1
.
5
Magnetized
Bit 1 of
06.17
Drive status word 2
.
6
Running
Bit 6 of
06.16
Drive status word 1
.
7
Ready ref
Bit 2 of
06.11 Main status word
.
8
At setpoint
Bit 8 of
06.11 Main status word
.
9
Reverse
Bit 2 of
06.19
Speed control status word
.
10
Zero speed
Bit 0 of
06.19
Speed control status word
.
11
Above limit
Bit 10 of
06.17 Drive status word 2
.
12
Warning
Bit 7 of
06.11
Main status word
.
13
Fault
Bit 3 of
06.11
Main status word
.
14
No.
Name/Value
Description
Default
FbEq 16
Bit
Value
0
1 = Force DIO1 to value of bit 0 of parameter
11.04
DIO force data
.
1
1 = Force DIO2 to value of bit 1 of parameter
11.04
DIO force data
.
2...15
Reserved
Bit
Value
0
Set state of DIO1.
1
Set state of DIO2.
2...15
Reserved