248 Parameters
Ni1000
Ni1000 sensor connected to the analog input selected by
parameter
35.14
Temperature 1 AI source
and an analog
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to
U
(voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection
parameter in group
12 Standard AI
to
V
(volt).
• In parameter group
13 Standard AO
, set the source
selection parameter of the analog output to
Temp
sensor 1 excitation
.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along
with its temperature, the voltage over the sensor
increases. The voltage is read by the analog input and
converted into degrees.
16
35.12
Temperature 1 fault
limit
Defines the fault limit for temperature supervision
function 1. The unit is selected by parameter
96.16
Unit
selection
.
Note:
With a PTC sensor, the unit is ohms.
130 °C
-60…5000 °C
Fault limit for temperature monitoring function 1.
1 = 1 unit
35.13
Temperature 1
warning limit
Defines the warning limit for temperature supervision
function 1. The unit is selected by parameter
96.16
Unit
selection
.
Note:
With a PTC sensor, the unit is ohms.
110 °C
-60…5000 °C
Warning limit for temperature monitoring function 1.
1 = 1 unit
35.14
Temperature 1 AI
source
Selects the input for parameter
35.11 Temperature 1
source
selections
1 x Pt100 analog I/O
,
2 x Pt100 analog
I/O
,
3 x Pt100 analog I/O
, and
Direct temperature.
Not selected
Not selected
None.
0
AI1 actual value
Analog input AI1.
1
AI2 actual value
Analog input AI2.
2
Other
Source selection (see
Terms and abbreviations
).
-
35.21
Temperature 2 source
Selects the source from which measured temperature 2 is
read.
Usually this source is from a sensor connected to the
motor controlled by the drive, but it could be used to
measure and monitor a temperature from other parts of
the process as long as a suitable sensor is used as per
the selection list.
Disabled
Disabled
None. Temperature monitoring function 2 is disabled.
0
Estimated temperature Estimated motor temperature (see parameter
35.01 Motor
estimated temperature
).
The temperature is estimated from an internal drive
calculation. It is important to set up the ambient
temperature of the motor in
35.50 Motor ambient
temperature
.
1
Direct temperature
The temperature is taken from the source selected by
parameter
35.24 Temperature 2 AI source
. The value of
the source is assumed to be degrees Celsius.
11
No.
Name/Value
Description
Default
FbEq 16
ACS380 FW.book Page 248 Friday, May 4, 2018 4:18 PM