50.16
FBA A status word
Displays the raw (unmodified) status word sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter
50.12
FBA A debug mode
.
This parameter is read-only.
-
00000000h…
FFFFFFFFh
Status word sent by fieldbus adapter A to master.
-
50.17
FBA A actual value 1
Displays raw (unmodified) actual value ACT1 sent by
fieldbus adapter A to the master (PLC) if debugging is
enabled by parameter
50.12
FBA A debug mode
.
This parameter is read-only.
-
-2147483648…
2147483647
Raw ACT1 sent by fieldbus adapter A to master.
-
50.18
FBA A actual value 2
Displays raw (unmodified) actual value ACT2 sent by
fieldbus adapter A to the master (PLC) if debugging is
enabled by parameter
50.12
FBA A debug mode
.
This parameter is read-only.
-
-2147483648…
2147483647
Raw ACT2 sent by fieldbus adapter A to master.
-
51
51 FBA A settings
Fieldbus adapter A configuration.
51.01
FBA A type
Displays the type of the connected fieldbus adapter
module.
0
= Module is not found or is not properly connected, or is
disabled by parameter
50.01
FBA A enable
;
0
= None;
1
= PROFIBUS DP;
32
= CANopen;
37
= DeviceNet;
128 =
Ethernet;
132
= PROFINET IO;
135
= EtherCAT;
136
= ETH Pwrlink;
485
= RS-485 comm;
101
= ControlNet;
This parameter is read-only.
-
51.02
FBA A Par2
Parameters
51.02
…
51.26
are adapter module-specific.
For more information, see the documentation of the
fieldbus adapter module. Note that not all of these
parameters are necessarily in use.
-
0…65535
Fieldbus adapter configuration parameter.
1 = 1
…
…
…
…
51.26
FBA A Par26
See parameter
51.02
FBA A Par2
.
-
0…65535
Fieldbus adapter configuration parameter.
1 = 1
51.27
FBA A par refresh
Validates any changed fieldbus adapter module
configuration settings. After refreshing, the value reverts
automatically to
Done
.
Note:
This parameter cannot be changed while the drive
is running.
Done
Done
Refreshing done.
0
Configure
Refreshing.
1
51.28
FBA A par table ver
Displays the parameter table revision of the fieldbus
adapter module mapping file (stored in the memory of the
drive).
In format axyz, where ax = major table revision number;
yz = minor table revision number.
This parameter is read-only.
-
Parameter table revision of adapter module.
-