146 Parameters
13
13 Standard AO
Configuration of standard analog outputs.
13.02
AO force selection
Selects the analog outputs that will be forced to values
defined by parameters.
The true source signals of the analog outputs can be
overridden for eg. testing purposes. A forced value
parameter is provided for each analog output, and its
value is applied whenever the corresponding bit in this
parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
13.02
and
13.11
).
0000h
0000h…FFFFh
Forced values selector for analog output AO1.
1 = 1
13.11
AO1 actual value
Displays the value of AO1 in mA.
This parameter is read-only.
-
0.000…22.000 mA
Value of AO1.
1 = 1 mA
13.12
AO1 source
Selects a signal to be connected to analog output AO1.
Output
frequency
Zero
None. 0
Motor speed used
01.01 Motor speed used
1
Output frequency
01.06
Output frequency
3
Motor current
01.07
Motor current
4
Motor current % of
motor nom
01.08
Motor current % of motor nom
5
Motor torque
01.10
Motor torque
6
DC voltage
01.11
DC voltage
7
Output power
01.14 Output power
8
Speed ref ramp in
23.01
Speed ref ramp input
.
10
Speed ref ramp out
23.02
Speed ref ramp output
11
Speed ref used
24.01 Used speed reference
12
Freq ref used
28.02
Frequency ref ramp output
14
Process PID out
40.01 Process PID output actual
16
Temp sensor 1
excitation
The output is used to feed an excitation current to the
temperature sensor 1, see parameter
35.11
Temperature
1 source
. See also section
Motor thermal protection
.
20
Temp sensor 2
excitation
The output is used to feed an excitation current to the
temperature sensor 2, see parameter
35.21
Temperature
2 source
. See section
Motor thermal protection
in chapter
Program features
.
21
Abs motor speed used
01.61
Abs motor speed used
26
Abs motor speed %
01.62 Abs motor speed %
27
Abs output frequency
01.63
Abs output frequency
28
Abs motor torque
01.64 Abs motor torque
30
No.
Name/Value
Description
Default
FbEq 16
Bit
Value
0
1 = Force AO1 to value of parameter
13.13
AO1 forced value
.
1…15
Reserved.
ACS380 FW.book Page 146 Friday, May 4, 2018 4:18 PM