Parameters 273
Other
Source selection (see
Terms and abbreviations
on page
112
).
-
40.89
Set 1 setpoint
multiplier
Defines the multiplier with which the result of the function
specified by parameter
40.18
Set 1 setpoint function
is
multiplied.
1.00
-200000.00…
200000.00
Multiplier.
1 = 1
40.90
Set 1 feedback
multiplier
Defines the multiplier with which the result of the function
specified by parameter
40.10
Set 1 feedback function
is
multiplied.
1.00
-200000.00…
200000.00
Multiplier.
1 = 1
40.91
Feedback data
storage
Storage parameter for receiving a process feedback value
eg. through the embedded fieldbus interface.
The value can be sent to the drive as Modbus I/O data.
Set the target selection parameter of that particular data
(
58.101
…
58.114
) to
Feedback data storage
. In
40.08
Set
1 feedback 1 source
(or
40.09
Set 1 feedback 2 source
),
select
Feedback storage
.
0.00
-327.68 … 327.67
Storage parameter for process feedback.
100 = 1
40.92
Setpoint data storage
Storage parameter for receiving a process setpoint value
eg. through the embedded fieldbus interface.
The value can be sent to the drive as Modbus I/O data.
Set the target selection parameter of that particular data
(
58.101
…
58.114
) to
Setpoint data storage
. In
40.16
Set 1
setpoint 1 source
(or
40.17
Set 1 setpoint 2 source
),
select
Setpoint data storage
.
0.00
-327.68 … 327.67
Storage parameter for process setpoint.
100 = 1
40.96
Process PID output %
Percentage scaled signal of parameter
40.01
Process PID
feedback actual
.
0.00%
-100.00…100.00%
Percentage.
100 = 1%
40.97
Process PID feedback
%
Percentage scaled signal of parameter
40.02
Process PID
feedback actual
.
0.00%
-100.00…100.00%
Percentage.
100 = 1%
40.98
Process PID setpoint
%
Percentage scaled signal of parameter
40.03
Process PID
setpoint actual
.
0.00%
-100.00…100.00%
Percentage.
100 = 1%
40.99
Process PID deviation
%
Percentage scaled signal of parameter
40.04
Process PID
deviation actual
.
0.00%
-100.00…100.00%
Percentage.
100 = 1%
41
41 Process PID set 2
A second set of parameter values for process PID control.
The selection between this set and first set (parameter
group
40 Process PID set 1
) is made by parameter
40.57
PID set1/set2 selection
.
See also parameters
40.01
…
40.06
, and the control chain
diagrams on pages
506
and
507
.
41.08
Set 2 feedback 1
source
See parameter
40.08
Set 1 feedback 1 source
.
Not selected
No.
Name/Value
Description
Default
FbEq 16
ACS380 FW.book Page 273 Friday, May 4, 2018 4:18 PM