Parameters 149
13.20
AO1 out at AO1 src
max
Defines the maximum output value for analog output AO1.
See also drawing at parameter
13.17 AO1 source min
.
20.000 mA
0.000…22.000 mA
0.000…11.000 V
Maximum AO1 output value.
1000 = 1 mA
13.91
AO1 data storage
Storage parameter for controlling analog output AO1 eg.
through the embedded fieldbus interface.
In parameter
13.12 AO1 source
, select
AO1 data storage
.
Then set this parameter as the target of the incoming
value data. With the embedded fieldbus interface, set the
target selection parameter of that particular data
(
58.101
…
58.114
to
AO1 data storage
).
0.00
-327.68 … 327.67
Storage parameter for AO1.
100 = 1
15
15 I/O extension module
Configuration of the I/O extension module.
Note:
The contents of the parameter group vary according
to the selected I/O extension module type.
15.01
Extension module type
Activates (and specifies the type of) I/O extension module.
If the value is
None
, when an extension module has been
installed and the dive is powered, the drive automatically
sets the value to the type it has detected (= value of
parameter
15.02
Detected extension module
); otherwise
warning
A7AB
Extension I/O configuration failure
is
generated and you have to set the value of this parameter
manually.
None
None
Inactive.
0
BREL
External relay option BREL-01.
5
BAPO-01
Auxiliary power extension module option BAPO-01.
6
BTAC-02
BTAC-02 pulse encoder interface module option BTAC-
02.
7
15.02
Detected extension
module
Shows the I/O extension module that the control program
has automatically detected on the drive.
None
None
Inactive.
0
BREL
External relay option BREL-01.
5
BAPO-01
Auxiliary power extension module option BAPO-01.
6
BTAC-02
Pulse encoder interface module option BTAC-02.
7
15.04
RO status
Displays the status of the relay outputs RO2, RO3, RO4
and RO5 on the extension module.
-
0000h…FFFFh
Status of relay outputs.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
Bit
Value
0
Status of RO2 (1= relay closed, 0=relay open)
1
Status of RO3 (1= relay closed, 0=relay open)
2
Status of RO4 (1= relay closed, 0=relay open)
3
Status of RO5 (1= relay closed, 0=relay open)
4...15
Reserved