212 Parameters
28.57
Critical frequency 3
high
Defines the high limit for critical frequency 3.
Note:
This value must be greater than or equal to the
value of
28.56
Critical frequency 3 low
.
0.00 Hz
-500.00…500.00 Hz
High limit for critical frequency 3.
See par.
46.02
28.71
Freq ramp set
selection
Selects a source that switches between the two sets of
acceleration/deceleration times defined by parameters
28.72
…
28.75
.
0 = Acceleration time 1 and deceleration time 1 are in
force.
1 = Acceleration time 2 and deceleration time 2 are in
force.
Note:
The default value depends on the selected macro.
See chapter
Control macros
on page
31
.
Acc/Dec time
1
Acc/Dec time 1
0
0
Acc/Dec time 2
1
1
DI1
Digital input DI1 (
10.02
DI delayed status
, bit 0).
2
DI2
Digital input DI2 (
10.02
DI delayed status
, bit 1).
3
DI3
Digital input DI3 (
10.02
DI delayed status
, bit 2).
4
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
5
DIO1
Digital input/output DIO1 (
11.02
DIO delayed status,
bit 0). 10
DIO2
Digital input/output DIO2 (
11.02
DIO delayed status,
bit 1). 11
FBA A
Only for the Transparent16 or Transparent32 profile.
Transparent16 or Transparent32 control word bit received
through the fieldbus A interface.
18
EFB DCU CW bit 10
Only for the DCU profile. DCU control word bit 10 received
through the embedded fieldbus interface.
20
Other [bit]
Source selection (see
Terms and abbreviations
).
-
28.72
Freq acceleration time
1
Defines acceleration time 1 as the time required for the
frequency to change from zero to the frequency defined
by parameter
46.02
Frequency scaling
. After this
frequency has been reached, the acceleration continues
with the same rate to the value defined by parameter
30.14
Maximum frequency
.
If the reference increases faster than the set acceleration
rate, the motor will follow the acceleration rate.
If the reference increases slower than the set acceleration
rate, the motor frequency will follow the reference.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to
exceed the drive torque limits.
3.000 s
0.000…1800.000 s
Acceleration time 1.
10 = 1 s
No.
Name/Value
Description
Default
FbEq 16
ACS380 FW.book Page 212 Friday, May 4, 2018 4:18 PM