186 Parameters
22.56
Critical speed 3 low
Defines the low limit for critical speed range 3.
Note:
This value must be less than or equal to the value
of parameter
22.57
.
0.00 rpm
-30000.00… 30000.00
rpm
Low limit for critical speed 3.
See par.
46.01
22.57
Critical speed 3 high
Defines the high limit for critical speed range 3.
Note:
This value must be greater than or equal to the
value of parameter
22.56
.
0.00 rpm
-30000.00… 30000.00
rpm
High limit for critical speed 3.
See par.
46.01
22.71
Motor potentiometer
function
Activates and selects the mode of the motor
potentiometer.
See section
Speed control performance figures
in chapter
Program features
.
Disabled
Disabled
Motor potentiometer is disabled and its value set to 0.
0
Enabled (init at power-
up)
When enabled, the motor potentiometer first adopts the
value defined by parameter
22.72
. The value can then be
adjusted from the up and down sources defined by
parameters
22.73
and
22.74
.
A power cycle will reset the motor potentiometer to the
predefined initial value (
22.72
).
1
Enabled (resume
always)
As
Enabled (init at power-up)
, but the motor potentiometer
value is retained over a power cycle.
2
Enabled (init to actual) Whenever another reference source is selected, the value
of the motor potentiometer follows that reference. After the
source of reference returns to the motor potentiometer, its
value can again be changed by the up and down sources
(defined by
22.73
and
22.74
).
3
22.72
Motor potentiometer
initial value
Defines an initial value (starting point) for the motor
potentiometer. See the selections of parameter
22.71
.
0.00
-32768.00… 32767.00 Initial value for motor potentiometer.
1 = 1
22.73
Motor potentiometer
up source
Selects the source of motor potentiometer up signal.
0 = No change
1 = Increase motor potentiometer value. (If both the up
and down sources are on, the potentiometer value will not
change.)
Not selected
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
10.02
DI delayed status
, bit 0).
2
DI2
Digital input DI2 (
10.02
DI delayed status
, bit 1).
3
DI3
Digital input DI3 (
10.02
DI delayed status
, bit 2).
4
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
5
DIO1
Digital input/output DIO1 (
11.02
DIO delayed status
, bit 0) 10
DIO2
Digital input/output DIO2 (
11.02
DIO delayed status
, bit 0) 11
Timed function 1
Bit 0 of
34.01 Timed functions status
.
18
Timed function 2
Bit 1 of
34.01 Timed functions status
.
19
Timed function 3
Bit 2 of
34.01 Timed functions status
.
20
Supervision 1
Bit 0 of
32.01 Supervision status
.
24
No.
Name/Value
Description
Default
FbEq 16