Fieldbus control through the embedded fieldbus interface (EFB) 445
The new settings will take effect when the drive is powered up the next time, or when
they are validated by parameter
58.06
Communication control
(
Refresh settings
).
Setting the drive control parameters
After the embedded fieldbus interface has been set up, check and adjust the drive
control parameters listed in the table below. The
Setting for fieldbus control
column
gives the value or values to use when the embedded fieldbus signal is the desired
source or destination for that particular drive control signal. The
Function/Information
column gives a description of the parameter.
58.80
58.86
58.92
TPDO1 transmission type
TPDO6 transmission type
TPDO21 transmission type
255 (default)
Defines the transmission type of
the PDO.
0 = acyclic synchronous
1...240 = cyclic synchronous
252 = synchronous RTR only
253 = asynchronous RTR only
254…255 = asynchronous
58.81
58.87
58.93
TPDO1 event timer
TPDO6 event timer
TPDO21 event timer
100 (default for
58.81
)
0 (default for
58.87
,
58.93
)
Defines the time-out time for the
PDO.
0 = no timeout
other = if this PDO is enabled and
has not been transmitted for
event timer milliseconds, a
transmission is forced
58.101
…
58.114
TPDO1 word 1
…
RPDO21 word 4
With the default
settings, TPDO1
contains 16-bit
status word and
two 16-bit actual
values and
RPDO1 contains
16-bit control word
and two 16-bit
reference values.
Defines the objects mapped to
PDOs to and from the drive.
58.06
Communication control
Refresh settings
Validates the settings of the
configuration parameters.
Parameter
Setting for
fieldbus control
Function/Information
CONTROL COMMAND SOURCE SELECTION
20.01
Ext1
commands
Embedded fieldbus
Selects fieldbus as the source for the start
and stop commands when EXT1 is selected
as the active control location.
20.02
Ext2
commands
Embedded fieldbus
Selects fieldbus as the source for the start
and stop commands when EXT2 is selected
as the active control location.
Parameter
Setting for
fieldbus control
Function/Information