![ABB ACS380 Series Скачать руководство пользователя страница 202](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560202.webp)
202 Parameters
DI2
Digital input DI2 (
10.02
DI delayed status
, bit 1).
4
DI3
Digital input DI3 (
10.02
DI delayed status
, bit 2).
5
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
6
DIO1
Digital input/output DIO1 (
11.02
DIO delayed status,
bit 0). 11
DIO2
Digital input/output DIO2 (
11.02
DIO delayed status,
bit 1). 12
Other [bit]
Source selection (see
Terms and abbreviations
).
-
26.17
Torque ref filter time
Defines a low-pass filter time constant for the torque
reference.
0.000 s
0.000…30.000 s
Filter time constant for torque reference.
1000 = 1 s
26.18
Torque ramp up time
Defines the torque reference ramp-up time, ie. the time for
the reference to increase from zero to nominal motor
torque.
0.000 s
0.000…60.000 s
Torque reference ramp-up time.
100 = 1 s
26.19
Torque ramp down
time
Defines the torque reference ramp-down time, ie. the time
for the reference to decrease from nominal motor torque
to zero.
0.000 s
0.000…60.000 s
Torque reference ramp-down time.
100 = 1 s
26.21
Torque sel torque in
Selects the source for
26.74 Torque ref ramp out
.
Torque ref
torq ctrl
Not selected
None.
0
Torque ref torq ctrl
Torque reference from the torque chain.
1
Other
Source selection (see
Terms and abbreviations
).
-
26.22
Torque sel speed in
Selects the source for
25.01 Torque reference speed
control
.
Torque ref
torq ctrl
Not selected
None.
0
Torque ref speed ctrl
Torque reference from the speed chain.
1
Other
Source selection (see
Terms and abbreviations
).
-
26.70
Torque reference act 1
Displays the value of torque reference source 1 (selected
by parameter
26.11 Torque ref1 source
). See the control
chain diagram on page
503
.
This parameter is read-only.
-
-1600.0…1600.0%
Value of torque reference source 1.
See par.
46.03
26.71
Torque reference act 2
Displays the value of torque reference source 2 (selected
by parameter
26.12 Torque ref2 source
). See the control
chain diagram on page
503
.
This parameter is read-only.
-
-1600.0…1600.0%
Value of torque reference source 2.
See par.
46.03
26.72
Torque reference act 3
Displays the torque reference after the function applied by
parameter
26.13 Torque ref1 function
(if any), and after
selection (
26.14
Torque ref1/2 selection
). See the control
chain diagram on page
503
.
This parameter is read-only.
-
-1600.0…1600.0%
Torque reference after selection.
See par.
46.03
No.
Name/Value
Description
Default
FbEq 16
ACS380 FW.book Page 202 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |
www.ghv.de